Liang Yue-wei, Liu Li-ru, Qi Rong-hui, et al. A Performance Study of Membrane Liquid Desiccant Air Conditioning System and Carbon Dioxide Transcritical Cycle Heat Pump Integrated System[J]. 2018, 35(1): 61-66.
Liang Yue-wei, Liu Li-ru, Qi Rong-hui, et al. A Performance Study of Membrane Liquid Desiccant Air Conditioning System and Carbon Dioxide Transcritical Cycle Heat Pump Integrated System[J]. 2018, 35(1): 61-66.DOI: 10.12052/gdutxb.170135.
A Performance Study of Membrane Liquid Desiccant Air Conditioning System and Carbon Dioxide Transcritical Cycle Heat Pump Integrated System
The direct contact liquid desiccant air conditioning driven by heat pump with freon as working fluid has the problem of air carrying desiccant solution
and this kind of working fluid is likely to destroy the environment. So an integrated system of membrane liquid desiccant air conditioner and carbon dioxide transcritical cycle heat pump system is presented
and the theoretical model of the system is established. The application of this system in a hotel in Guangzhou and the simulation analysis show that the integrated system performance coefficient EER is 8.8 and 0.65 for dehumidification efficiency. In full load condition
the design and performance difference of the "integrated system and dry air filter system of dry fan coil" and the "traditional fan coil and fresh air conditioning system" are compared and analyzed. The total power of the main equipment of the "integrated system and dry air filter system of dry fan coil" and the "traditional fan coil and fresh air conditioning system" are 74.3 kW and 90.5 kW
respectively. The air conditioning system based on the concept of THIC is 21.3% lower than the traditional fan coil plus fresh air conditioning system of electric power.
QI R H, LU L. Energy consumption and optimization of internally cooled/heated liquid desiccant air-conditioning system: A case study in Hong Kong[J]. Energy, 2014, 72: 801-808.
QI R H, LU L, HUANG Y. Parameter analysis and optimization of the energy and economic performance of solar-assisted liquid desiccant cooling system under different climate conditions[J]. Energy Conversion and Management, 2015, 106: 1387-1395.
刘晓华, 李震, 张涛, 等.溶液除湿[M]. 北京: 中国建筑工业出版社, 2014.
ABDEL-SALAM A H, SIMONSON C J. Capacity matching in heat-pump membrane liquid desiccant air conditioning systems[J]. International Journal of Refrigeration, 2014, 48: 166-177.
ZHANG L Z, ZHANG N. A heat pump driven and hollow fiber membrane-based liquid desiccant air dehumidification system[J]. Energy, 2014, 65: 441-451.
AUSTIN B T, SUMATHY K. Transcritical carbon dioxide heat pump system: A review[J]. Renewable and Sustainable Energy Reviews, 2011, 15: 4013-4029.
PEARSON A. Carbon dioxide-new uses for an old refrigerant[J]. International Journal of Refrigeration, 2005, 28: 1140-1148.
JAKOBSEN A, RASMUSSEN B D, ANDERSEN S E. CoolPack-Simulation tools for refrigeration systems[J]. Scan Ref, 1999, 28: 7-10.
SARKAR J, BHATTACHARYYA S, GOPAL M R. Simulation of a transcritical CO 2 heat pump cycle for simultaneous cooling and heating applications[J ] . International Journal of Refrigeration, 2006, 29: 735-743.
INCROPERA F P, DEWITT D P. Fundamentals of heat and mass transfer[M]. New York: John Wiley Sons, 2007.
LIU L R, LYU C H, WANG X X.Energy flow model analysis of central air conditioning system for water-cooled chiller[J]. Journal of Guangdong University of Technology, 2015, 32(1): 38-41.
CHEN T, LIU L R, WANG Z Y, et al . Simulation study of CO 2 transcritical cycle heat pump system used in temperature and humidity independent control air conditioning system[J ] . Journal of Guangdong University of Technology, 2017, 34(1): 40-44.
Kim M H, Pettersen J, Bullard C W. Fundamental process and system design ossues in CO 2 vapor compression systems[J ] . Progress in Energy and Combustion Science, 2004, 30(2): 119-174.
ZHANG X P, XU B Q, TIAN X D, et al . Research on nominal working condition, temperature condition and basic specification of "dry fan coil unit" standard[J ] . Fluid Machinery, 2011, 39(8): 59-63.