Simulation Analysis of Breakdown Characteristics in Isolation Switch Fracture in Same Frequency and Phase AC Withstand Voltage Test of 110 kV Three-Phase Cylindrical GIS
Power System|更新时间:2025-06-18
|
Simulation Analysis of Breakdown Characteristics in Isolation Switch Fracture in Same Frequency and Phase AC Withstand Voltage Test of 110 kV Three-Phase Cylindrical GIS
Electric PowerVol. 54, Issue 7, Pages: 117-124(2021)
Yifan QIN, Zheng NIU, Yunsheng SUN, et al. Simulation Analysis of Breakdown Characteristics in Isolation Switch Fracture in Same Frequency and Phase AC Withstand Voltage Test of 110 kV Three-Phase Cylindrical GIS[J]. Electric power, 2021, 54(7): 117-124.
DOI:
Yifan QIN, Zheng NIU, Yunsheng SUN, et al. Simulation Analysis of Breakdown Characteristics in Isolation Switch Fracture in Same Frequency and Phase AC Withstand Voltage Test of 110 kV Three-Phase Cylindrical GIS[J]. Electric power, 2021, 54(7): 117-124. DOI: 10.11930/j.issn.1004-9649.201912075.
Simulation Analysis of Breakdown Characteristics in Isolation Switch Fracture in Same Frequency and Phase AC Withstand Voltage Test of 110 kV Three-Phase Cylindrical GIS
The same frequency and phase AC withstand voltage test technology has been widely used in the insulation performance test of inspection or expansion in 220kV Gas Insulated Switchgear (GIS)
which can avoid stopping running grid bus of the system. However
the technology has been promoted in the withstand voltage test of GIS equipment with 110 kV voltage level. The three-phase cylindrical structure is generally adopted in 110 kV GIS devices. Due to the small inter-phase space
the switch has a higher risk of breakdown when the three-station disconnecting switch is subjected to the withstand voltage test. In this paper
the EMTP-ATP simulation software is used to construct the breakdown model of 110 kV GIS equipment in the same frequency and phase AC withstand voltage test. The fault voltage and current characteristics of the same phase and wrong phase is obtained. The influence of the installation protection resistances on the breakdown characteristics is analyzed
and the suggestions for suppression of the breakdown characteristics are given. This paper can provide useful references for the application of the same frequency and phase technology in the AC withstand voltage test of 110 kV GIS equipment.
HU Quanyi, MI Lipeng, LIU Tianqi, et al . A case of insulated swithgear equipment air leakage and site AC withstand voltage test breakdown fault analysis.[J ] . Electrotechnics Electric, 2017(8): 43–46.
GU Qiang, JIN Xin, YUAN Ting, et al . Development and application for an AC withstand voltage equipment without power outage of GIS[J ] . Electric Power, 2017, 50(10): 83–88.
MA Yunlong, HAO Jinpeng, LI Xiuguang, et al . Research and application of the same frequency and phase AC withstand voltage test technique of GIS[J ] . Electrical Engineering, 2016(10): 111–114.
YANG Xinchun, QIU Wei, HUANG Kun, et al . Risk analysis and suppression measure of same frequency and phase withstand voltage test of gas insulated switchgear equipment[J ] . Electrotechnics Electric, 2017(2): 52–55.
CHEN Zhibin, LIU Jingbo, LUO Hu, et al . A new type of 3-phase in one enclosure 126 kV GIS with compact and reliable performance[J ] . High Voltage Apparatus, 2009, 45(3): 113–116.
ZHENG Y ibo, XU Dangguo, QIN Yifan, et al . The distribution of electric field in the three-station disconnecting switch in same frequency and phase AC withstand voltage test of 110 kV GIS[J ] . Electric Power, 2020, 53(2): 43–48.
WANG Qian, WU Gaolin, XU Ruilin, et al . Simulation and prevention of isolating distance breakdown in busbar during power frequency withstand test for GIS[J ] . High voltage Appartus, 2013, 49(4): 98–104.
WANG Lujun, MAO Xing, TANG Zhiyu. Research on the method of GIS for the same frequency and phase AC voltage withstanding test[J]. Information Technology Research, 2016, 42(5): 62–65.
XUE Feng, PAN Qi, PAN Xiaoming, et al . Analysis of relay action caused by an Internal fault in 220 kV GIS equipment[J ] . Jiangsu Electrical Engineering, 2011, 30(04): 18–20.
LIU Suisheng, LU He, YAN Shengli, et al . Partial discharge characteristics of gas-gap defect within insulator in GIS on UHF method[J ] . Science Technology and Engineering, 2013, 13(32): 9692–9696.
WANG Qian, YE Zan, Tan Wangjing, et al . Simulation and analysis of accurate breakdown arc model[J ] . Power System and Clean Energy, 2015, 31(10): 4–8.
李进. 高压隔离开关高频电弧建模分析研究[J]. 电工技术, 2019(20): 23–25.
LI Jin. Modeling and analysis of high frequency arc of high voltage isolation switch[J]. Electric Engineering, 2019(20): 23–25.
张雪. GIS设备VFTO仿真中隔离开关电弧模型的研究[D]. 北京: 华北电力大学, 2010.
ZHANG Xue. The research on the arc model in disconnector switch for VFTO simulation in GIS[D]. Beijing: North China Electric Power University, 2010.
POVH D, SCHMITT H, VOLCKER O, et al . Modeling and analysis guidelines for very fast transients[J ] . IEEE Power Engineering Review, 1996, 16(10): 71.