An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response
Original Research|更新时间:2026-09-30
|
An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response
Protection and Control of Modern Power SystemsVol. 8, Issue 3, Pages: 1-11(2023)
作者机构:
1. State Key Laboratory of Power Transmission Equipment and System Security and New Technology, School of Electrical Engineering, Chongqing University,Chongqing,China
2. Electric Power Research Institute of State Grid Henan Electric Power Company, Zhenazhou,China
3. Chongqing City Management College,Chongqing,China
Jinxin Ouyang, Xinyu Pan, Junjun Ye, et al. An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response[J]. Protection and Control of Modern Power Systems, 2023, 8(3): 1-11.
DOI:
Jinxin Ouyang, Xinyu Pan, Junjun Ye, et al. An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response[J]. Protection and Control of Modern Power Systems, 2023, 8(3): 1-11.DOI: 10.1186/s41601-023-00323-9.
An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response
Subsequent commutation failure (SCF) can be easily generated during the first commutation failure (CF) recovery process in a line-commutated converter-based high voltage direct-current system. SCF poses a significant threat to the safe and stable operation of power systems
and accurate prediction of CF is thus important. However
SCF is affected by the operating characteristics of the main circuit and the coupling effects of sequential control response in the inverter station. These are difficult to predict accurately. In this paper
a new SCF prediction method considering the control response is proposed based on the physical principle of SCF. The time sequence and switching conditions of the controllers at different stages of the first CF recovery process are described
and the corresponding equations of commutation voltage affected by different controllers are derived. The calculation method of the SCF threshold voltage is proposed
and the prediction method is established. Simulations show that the proposed method can predict SCF accurately and provide useful tools to suppress SCF.
Abstract
Subsequent commutation failure (SCF) can be easily generated during the frst commutation failure (CF) recovery process in a line-commutated converter-based high voltage direct-current system. SCF poses a signifcant threat to the safe and stable operation of power systems
and accurate prediction of CF is thus important. However
SCF is afected by the operating characteristics of the main circuit and the coupling efects of sequential control response in the inverter station. These are difcult to predict accurately. In this paper
a new SCF prediction method considering the control response is proposed based on the physical principle of SCF. The time sequence and switching conditions of the controllers at diferent stages of the frst CF recovery process are described
and the corresponding equations of commutation voltage afected by diferent controllers are derived. The calculation method of the SCF threshold voltage is proposed
and the prediction method is established. Simulations show that the proposed method can predict SCF accurately and provide useful tools to suppress SCF