Dual degree branched type-2 fuzzy controller optimized with a hybrid algorithm for frequency regulation in a triple-area power system integrated with renewable sources
Original Research|更新时间:2026-09-30
|
Dual degree branched type-2 fuzzy controller optimized with a hybrid algorithm for frequency regulation in a triple-area power system integrated with renewable sources
Protection and Control of Modern Power SystemsVol. 8, Issue 3, Pages: 1-29(2023)
作者机构:
1. Department of Electrical Engineering, Indian Institute of Technology (Indian School of Mines), Dhanbad,India
2. Department of Electrical Engineering, National Institute of Technology, Patna,India
3. Department of Electrical Engineering, J.C. Bose University of Science and Technology, YMCA, Faridabad, Haryana,India
Nisha Kumari, Pulakraj Aryan, G. Lloyds Raja, et al. Dual degree branched type-2 fuzzy controller optimized with a hybrid algorithm for frequency regulation in a triple-area power system integrated with renewable sources[J]. Protection and Control of Modern Power Systems, 2023, 8(3): 1-29.
DOI:
Nisha Kumari, Pulakraj Aryan, G. Lloyds Raja, et al. Dual degree branched type-2 fuzzy controller optimized with a hybrid algorithm for frequency regulation in a triple-area power system integrated with renewable sources[J]. Protection and Control of Modern Power Systems, 2023, 8(3): 1-29.DOI: 10.1186/s41601-023-00317-7.
Dual degree branched type-2 fuzzy controller optimized with a hybrid algorithm for frequency regulation in a triple-area power system integrated with renewable sources
The uncertainties associated with multi-area power systems comprising both thermal and distributed renewable generation (DRG) sources such as solar and wind necessitate the use of an efficient load frequency control (LFC) technique. Therefore
a hybrid version of two metaheuristic algorithms (arithmetic optimization and African vulture's optimization algorithm) is developed. It is called the ‘arithmetic optimized African vulture's optimization algorithm (AOAVOA). This algorithm is used to tune a novel type-2 fuzzy-based proportional-derivative branched with dual degree-of-freedom proportional-integral-derivative controller for the LFC of a three-area hybrid deregulated power system. Thermal
electric vehicle (EV)
and DRG sources (including a solar panel and a wind turbine system) are connected in area-1. Area-2 involves thermal and gas-generating units (GUs)
while thermal and geothermal units are linked in area-3. Practical restrictions such as thermo-boiler dynamics
thermal-governor dead-band
and generation rate constraints are also considered. The proposed LFC method is compared to other controllers and optimizers to demonstrate its superiority in rejecting step and random load disturbances. By functioning as energy storage elements
EVs and DRG units can enhance dynamic responses during peak demand. As a result
the effect of the aforementioned units on dynamic reactions is also investigated. To validate its effectiveness
the closed-loop system is subjected to robust stability analysis and is compared to various existing control schemes from the literature. It is determined that the suggested AOAVOA improves fitness by 40.20% over the arithmetic optimizer (AO)
while frequency regulation is improved by 4.55% over an AO-tuned type-2 fuzzy-based branched controller.
Abstract
The uncertainties associated with multi-area power systems comprising both thermal and distributed renewable generation (DRG) sources such as solar and wind necessitate the use of an efcient load frequency control (LFC) technique. Therefore
a hybrid version of two metaheuristic algorithms (arithmetic optimization and African vulture’s optimization algorithm) is developed. It is called the ‘arithmetic optimized African vulture’s optimization algorithm (AOAVOA)’. This algorithm is used to tune a novel type-2 fuzzy-based proportional–derivative branched with dual degree-of-freedom proportional–integral–derivative controller for the LFC of a three-area hybrid deregulated power system. Thermal
electric vehicle (EV)
and DRG sources (including a solar panel and a wind turbine system) are connected in area-1. Area-2 involves thermal and gas-generating units (GUs)
while thermal and geothermal units are linked in area-3. Practical restrictions such as thermo-boiler dynamics
thermal-governor dead-band
and generation rate constraints are also considered. The proposed LFC method is compared to other controllers and optimizers to demonstrate its superiority in rejecting step and random load disturbances. By functioning as energy storage elements
EVs and DRG units can enhance dynamic responses during peak demand. As a result
the efect of the aforementioned units on dynamic reactions is also investigated. To validate its efectiveness
the closed-loop system is subjected to robust stability analysis and is compared to various existing control schemes from the literature. It is determined that the suggested AOAVOA improves ftness by 40.20% over the arithmetic optimizer (AO)
while frequency regulation is improved by 4.55% over an AO-tuned type-2 fuzzy-based branched controller.
An Interactive Operating Demand Response Approach for Hybrid Power Systems Integrating Renewable Energy Sources
Coordination control method to block cascading failure of a renewable generation power system under line dynamic security
Coordinated control of conventional powersources and PHEVs using jaya algorithmoptimized PID controller for frequencycontrol of a renewable penetrated powersystem
Robust frequency control in a renewablepenetrated power system: an adaptivefractional order-fuzzy approach
Microgrid dynamic security consideringhigh penetration of renewable energy
Related Author
Abhishek Saxena
Ravi Shankar
Jinxin Ouyang
Jianfeng Yu
Xiaoxuan Long
Yanbo Diao
Jian Wang
Anil Annamraju
Related Institution
State Key Laboratory of Power Transmission Equipment and System Security and New Technology, School of Electrical Engineering, Chongqing University
Information and Communication Branch of State Grid, Chongqing Electric Power Company
Chongqing City Management College
Department of Electrical Engineering, National Institute of Technology Warangal, Warangal, Telangana
Department of Electrical Engineering, Kyushu Institute of Technology, Kitakyushu-, Fukuoka