Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
Original Research|更新时间:2026-09-30
|
Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
Protection and Control of Modern Power SystemsVol. 8, Issue 2, Pages: 1-11(2023)
作者机构:
1. Yunnan Key Laboratory of Green Energy, Electric Power Measurement Digitalization, Control and Protection, Kunming University of Science and Technology,Yunnan Province,Kunming,China
2. School of Electrical Engineering and Automation, Harbin Institute of Technology,Heilongjiang Province,Harbin,China
Hongchun Shu, Shixin Wang, Shunguang Lei. Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band[J]. Protection and Control of Modern Power Systems, 2023, 8(2): 1-11.
DOI:
Hongchun Shu, Shixin Wang, Shunguang Lei. Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band[J]. Protection and Control of Modern Power Systems, 2023, 8(2): 1-11.DOI: 10.1186/s41601-023-00301-1.
Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
Hybrid high-voltage direct current (HVDC) transmission has the characteristic of long transmission distance
complex corridor environment
and rapid fault evolution of direct current (DC) lines. As high fault current can easily cause irreversible damage to power devices
rapid and reliable line protection and isolation are necessary to improve the security and reliability of hybrid HVDC transmission system. To address such requirement
this paper proposes a single-ended protection method based on transient voltage frequency band characteristics. First
the frequency characteristics of the smoothing reactor
DC filter
and DC line are analyzed
and the characteristic frequency band is defined. A fault criterion is then constructed based on the voltage characteristic frequency band energy
and faulty pole selection is performed according to the fault voltage characteristic frequency band energy ratio. The proposed protection method is verified by simulation
and the results show that it can rapidly and reliably identify internal and external faults
accurately select faulty poles without data communication synchronization
and has good fault-resistance and anti-interference performance.
Abstract
Hybrid high-voltage direct current (HVDC) transmission has the characteristic of long transmission distance
complex corridor environment
and rapid fault evolution of direct current (DC) lines. As high fault current can easily cause irreversible damage to power devices
rapid and reliable line protection and isolation are necessary to improve the security and reliability of hybrid HVDC transmission system. To address such requirement
this paper proposes a single-ended protection method based on transient voltage frequency band characteristics. First
the frequency characteristics of the smoothing reactor
DC flter
and DC line are analyzed
and the characteristic frequency band is defned. A fault criterion is then constructed based on the voltage characteristic frequency band energy
and faulty pole selection is performed according to the fault voltage characteristic frequency band energy ratio. The proposed protection method is verifed by simulation
and the results show that it can rapidly and reliably identify internal and external faults
accurately select faulty poles without data communication synchronization
and has good fault-resistance and anti-interference performance.