Shan Cheng, Zihao Yu, Ye Liu, et al. Power system transient stability assessment based on the multiple paralleled convolutional neural network and gated recurrent unit[J]. Protection and Control of Modern Power Systems, 2022, 7(3): 1-16.
DOI:
Shan Cheng, Zihao Yu, Ye Liu, et al. Power system transient stability assessment based on the multiple paralleled convolutional neural network and gated recurrent unit[J]. Protection and Control of Modern Power Systems, 2022, 7(3): 1-16.DOI: 10.1186/s41601-022-00260-z.
Power system transient stability assessment based on the multiple paralleled convolutional neural network and gated recurrent unit
In order to accurately evaluate power system stability in a timely manner after faults
and further improve the feature extraction ability of the model
this paper presents an improved transient stability assessment (TSA) method of <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{CNN}+\text{GRU}$. This comprises a convolutional neural network (CNN) and gated recurrent unit (GRU). CNN has the feature extraction capability for a micro short-term time sequence
while GRU can extract characteristics contained in a macro long-term time sequence. The two are integrated to comprehensively extract the high-order features that are contained in a transient process. To overcome the difficulty of sample misclassification
a multiple parallel (MP) <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{CNN}+\text{GRU}$
with multiple <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{CNN + GRU}$ connected in parallel
is created. Additionally
an improved focal loss (FL) function which can implement self-adaptive adjustment according to the neural network training is introduced to guide model training. Finally
the proposed methods are verified on the IEEE 39 and 145-bus systems. The simulation results indicate that the proposed methods have better TSA performance than other existing methods.
Abstract
In order to accurately evaluate power system stability in a timely manner after faults
and further improve the feature extraction ability of the model
this paper presents an improved transient stability assessment (TSA) method of CNN + GRU. This comprises a convolutional neural network (CNN) and gated recurrent unit (GRU). CNN has the feature extraction capability for a micro short-term time sequence
while GRU can extract characteristics contained in a macro long-term time sequence. The two are integrated to comprehensively extract the high-order features that are contained in a transient process. To overcome the difficulty of sample misclassification
a multiple parallel (MP) CNN + GRU
with multiple CNN + GRU connected in parallel
is created. Additionally
an improved focal loss (FL) function which can implement self-adaptive adjustment according to the neural network training is introduced to guide model training. Finally
the proposed methods are verified on the IEEE 39 and 145-bus systems. The simulation results indicate that the proposed methods have better TSA performance than other existing methods.