Jigneshkumar Pramodbhai Desai, Vijay Hiralal Makwana. A novel out of step relaying algorithm based on wavelet transform and a deep learning machine model[J]. Protection and Control of Modern Power Systems, 2021, 6(4).
DOI:
Jigneshkumar Pramodbhai Desai, Vijay Hiralal Makwana. A novel out of step relaying algorithm based on wavelet transform and a deep learning machine model[J]. Protection and Control of Modern Power Systems, 2021, 6(4).DOI: 10.1186/s41601-021-00221-y.
A novel out of step relaying algorithm based on wavelet transform and a deep learning machine model
Out-of-step protection of one or a group of synchronous generators is unreliable in a power system which has significant renewable power penetration. In this work
an innovative out-of-step protection algorithm using wavelet transform and deep learning is presented to protect synchronous generators and transmission lines. The specific patterns are generated from both stable and unstable power swing
and three-phase fault using the wavelet transform technique. Data containing 27
008 continuous samples of 48 different features is used to train a two-layer feed-forward network. The proposed algorithm gives an automatic
setting free and highly accurate classification for the three-phase fault
stable power swing
and unstable power swing through pattern recognition within a half cycle. The proposed algorithm uses the Kundur 2-area system and a 29-bus electric network for testing under different swing center locations and levels of renewable power penetration. Hardware-in-the-loop (HIL) tests show the hardware compatibility of the developed out-of-step algorithm. The proposed algorithm is also compared with recently reported algorithms. The comparison and test results on different large-scale systems show that the proposed algorithm is simple
fast
accurate
and HIL tested
and not affected by changes in power system parameters.