Suryanarayana Gangolu, Saumendra Sarangi. A novel complex current ratio-basedtechnique for transmission line protection[J]. Protection and Control of Modern Power Systems, 2020, 5(3).
DOI:
Suryanarayana Gangolu, Saumendra Sarangi. A novel complex current ratio-basedtechnique for transmission line protection[J]. Protection and Control of Modern Power Systems, 2020, 5(3).DOI: 10.1186/s41601-020-00168-6.
A novel complex current ratio-basedtechnique for transmission line protection
the current differential scheme is a better way to protect transmission lines than overcurrent and distance-based schemes. However
the protection scheme can be severely influenced by the Line Charging Capacitive Current (LCCC) with increased voltage level and Current Transformer (CT) saturation under external close-in faults. This paper presents a new UHV/EHV current-based protection scheme using the ratio of phasor summation of the two-end currents to the local end current
instead of summation of the two-end currents
to discriminate the internal faults. The accuracy and effectiveness of the proposed protection technique are tested on the 110 kV Western System Coordinating Council (WSCC) 9-bus system using PSCAD/MATLAB. The simulation results confirm the reliable operation of the proposed scheme during internal/external faults and its independence from fault location
fault resistance
type of fault
and variations in source impedance. Finally
the effectiveness of the proposed scheme is also verified with faults during power swing and in series compensated lines.
Abstract
With respect to sensitivity
selectivity and speed of operation
the current differential scheme is a better way to protect transmission lines than overcurrent and distance-based schemes. However
the protection scheme can be severely influenced by the Line Charging Capacitive Current (LCCC) with increased voltage level and Current Transformer (CT) saturation under external close-in faults. This paper presents a new UHV/EHV current-based protection scheme using the ratio of phasor summation of the two-end currents to the local end current
instead of summation of the two-end currents
to discriminate the internal faults. The accuracy and effectiveness of the proposed protection technique are tested on the 110 kV Western System Coordinating Council (WSCC) 9-bus system using PSCAD/MATLAB. The simulation results confirm the reliable operation of the proposed scheme during internal/external faults and its independence from fault location
fault resistance
type of fault
and variations in source impedance. Finally
the effectiveness of the proposed scheme is also verified with faults during power swing and in series compensated lines.
A review of the protection for the multiterminalVSC-HVDC grid
IEC61850 standard-based harmonicblocking scheme for power transformers
Dual Alternative Iteration Algorithm-Based Hierarchical MPC Strategy for Frequency Regulation Control and Active Power Allocation of Wind-storage Coupling System
Real-Time Detection of Low-frequency Oscillations in Traction Power Supply Systems Based on Optimized Atomic Decomposition
Research on Fault Diagnosis of Asymmetric Three-Level T-Type Power Converter Based on Switched Reluctance Motor