A review of single phase adaptive autoreclosingschemes for EHV transmissionlines
Review|更新时间:2026-09-30
|
A review of single phase adaptive autoreclosingschemes for EHV transmissionlines
Protection and Control of Modern Power SystemsVol. 4, Issue 3, Pages: 1-10(2019)
作者机构:
1. State Key Laboratory for Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing, People's Republic of China
2. Faculty of Engineering, Lahore Leads University, Lahore, Punjab,Pakistan
Waqar Ahmad Khan, Tianshu Bi, Ke Jia. A review of single phase adaptive autoreclosingschemes for EHV transmissionlines[J]. Protection and Control of Modern Power Systems, 2019, 4(3): 1-10.
DOI:
Waqar Ahmad Khan, Tianshu Bi, Ke Jia. A review of single phase adaptive autoreclosingschemes for EHV transmissionlines[J]. Protection and Control of Modern Power Systems, 2019, 4(3): 1-10.DOI: 10.1186/s41601-019-0133-5.
A review of single phase adaptive autoreclosingschemes for EHV transmissionlines
Statistics shows that transients produced by lightning or momentary links with external objects
have produced more than 80% of faults in overhead lines. Reclosing of circuit breaker (CB) after a pre-defined dead time is very common however reclosing onto permanent faults may damage the power system stability and aggravate severe damage to the system. Thus
adaptive single-phase auto-reclosing (ASPAR) based on investigating existing electrical signals has fascinated engineers and researchers. An ASPAR blocks CB reclosing onto permanent faults and allows reclosing permission once secondary arc is quenched. To address the subject
there have been many ASPARs techniques proposed based on the features trapped in a faulty phase. This paper presents a critical survey of adaptive auto-reclosing schemes that have hitherto been applied to EHV transmission lines.
Abstract
Statistics shows that transients produced by lightning or momentary links with external objects
have produced more than 80% of faults in overhead lines. Reclosing of circuit breaker (CB) after a pre-defined dead time is very common however reclosing onto permanent faults may damage the power system stability and aggravate severe damage to the system. Thus
adaptive single-phase auto-reclosing (ASPAR) based on investigating existing electrical signals has fascinated engineers and researchers. An ASPAR blocks CB reclosing onto permanent faults and allows reclosing permission once secondary arc is quenched. To address the subject
there have been many ASPARs techniques proposed based on the features trapped in a faulty phase. This paper presents a critical survey of adaptive auto-reclosing schemes that have hitherto been applied to EHV transmission lines.