Corrosion Failure Analysis of Contactor Type Electrical Connection Components Used in Converter Valve Side Bushings
摘要
As a commonly used bushing current-carrying structure in recent years
contactor-type electrical connection parts operate in a complex environment of electric
thermal and chemical corrosion for extended periods. With the increase of ultra-high voltage (UHV) transmission capacity
its operating environment faces more stringent challenges
and the stability of their operation is directly linked to the reliability of the UHV transformer equipment. This paper aims to investigate the mechanism behind contact failure by developing a contactor deterioration test platform in oil to study the deterioration and corrosion process of strap contactor in oil under 120°C environment. The study found that the sulphur element content on the exposed copper surface of the strap contactor was elevated from 0% to 2.05% in 28 days
and there was an obvious latency period for the sulphide corrosive reaction with the surface of the strap contactor. The electrical contact resistance of the strap contactor after the corrosion reaction was elevated from 110 to 251 μΩ
which became overheating failure and contact failure of electrical connection components of bushings.
Abstract
As a commonly used bushing current-carrying structure in recent years
contactor-type electrical connection parts operate in a complex environment of electric
thermal and chemical corrosion for extended periods. With the increase of ultra-high voltage (UHV) transmission capacity
its operating environment faces more stringent challenges
and the stability of their operation is directly linked to the reliability of the UHV transformer equipment. This paper aims to investigate the mechanism behind contact failure by developing a contactor deterioration test platform in oil to study the deterioration and corrosion process of strap contactor in oil under 120°C environment. The study found that the sulphur element content on the exposed copper surface of the strap contactor was elevated from 0% to 2.05% in 28 days
and there was an obvious latency period for the sulphide corrosive reaction with the surface of the strap contactor. The electrical contact resistance of the strap contactor after the corrosion reaction was elevated from 110 to 251 μΩ
which became overheating failure and contact failure of electrical connection components of bushings.
Investigating Breathing Dynamics of a 110 kV Oil-Immersed Transformer Using Thermal-Fluid-Structure Interaction Modelling
Analysis of the Anti High-Altitude Electromagnetic Pulse Interference Ability of Relay Protection Devices
Low-Frequency Oscillation Suppression of FDR Time-Domain Diagnostic Waveforms for Cable Defects Based on Splicing Technology
Influence of Moisture on Electrical Properties of Fibre-Reinforced Polymer Core Rod in the Decay-Like Degraded Composite Insulator
Enhancing Hydrophobic Stability of Silicone Rubber Insulators Under High-Voltage Direct Current Stress Through Optimised Nano-Fumed Silica Surface Area: A Dynamic Drop Test Study