1. The Wind Solar Storage Division of State Key Laboratory of Control and Simulation of Power System and Generation Equipment, School of Electrical Engineering, Xinjiang University,Urumqi,China
2. The Tony Davis High Voltage Laboratory, University of Southampton,Southampton,UK
3. State Key Laboratory of Power System and Generation Equipment, Department of Electrical Engineering, Tsinghua University,Beijing,China
4. College of Electrical Engineering and Automation, Fuzhou University,Fuzhou,China
5. Yuanxiang Zhou
6. ,and
7. Yunxiao Zhang
Published:2025
移动端阅览
Ke Li, Luming Zhou, Guimin Jiang, et al. Significant Suppression of High Electric Field Regions in XLPE via Voltage Stabilisers[J]. High Voltage, 2025, 10(6).
Ke Li, Luming Zhou, Guimin Jiang, et al. Significant Suppression of High Electric Field Regions in XLPE via Voltage Stabilisers[J]. High Voltage, 2025, 10(6). DOI: 10.1049/hve2.70133.
Dielectric degradation typically originates from local defects. The resulting electric field concentration accelerates defect growth. Suppressing field distortion arising from such local weaknesses has long been a major challenge in electrical insulation. In this work
we incorporated the voltage stabiliser anthrone (ET) into cross-linked polyethylene (XLPE). This design enables field-driven adaptive migration and charge trapping
thereby dynamically regulating local electric fields. Space charge analysis reveals that ET captures charge and creates a reverse electric field. This process inhibits charge injection and transport
significantly reduces internal field distortion and results in a negative electric field coefficient effect. Notably
at 110 kV/mm the distortion ratio decreases from 118.6% in XLPE to only 0.05% in ET/XLPE
a reduction by more than 2000 times. These findings highlight the critical role of voltage stabilisers in enhancing dielectric reliability.
Dielectric degradation typically originates from local defects. The resulting electric field concentration accelerates defect growth. Suppressing field distortion arising from such local weaknesses has long been a major challenge in electrical insulation. In this work
we incorporated the voltage stabiliser anthrone (ET) into cross-linked polyethylene (XLPE). This design enables field-driven adaptive migration and charge trapping
thereby dynamically regulating local electric fields. Space charge analysis reveals that ET captures charge and creates a reverse electric field. This process inhibits charge injection and transport
significantly reduces internal field distortion and results in a negative electric field coefficient effect. Notably
at 110 kV/mm the distortion ratio decreases from 118.6% in XLPE to only 0.05% in ET/XLPE
a reduction by more than 2000 times. These findings highlight the critical role of voltage stabilisers in enhancing dielectric reliability.
0
Views
0
下载量
0
CSCD
Publicity Resources
Related Articles
Related Author
Related Institution
京公网安备11010802024621