Hang Wang, Haoran Zhang, Lei Li, et al. Partial Discharge Detection Method of Fibre-Composed HVDC Submarine Cable Based on φ-OTDR and Hilbert Demodulation[J]. High Voltage, 2025, 10(6).
Hang Wang, Haoran Zhang, Lei Li, et al. Partial Discharge Detection Method of Fibre-Composed HVDC Submarine Cable Based on φ-OTDR and Hilbert Demodulation[J]. High Voltage, 2025, 10(6). DOI: 10.1049/hve2.70123.
Partial discharge (PD) is the indicator of the insulation defect in cables. However
the pulse current method
which is widely adopted in land cables
cannot obtain PD signals of high-voltage direct current (HVDC) submarine cables due to attenuation and installation position. To detect the PD of the HVDC submarine cable
a PD vibration diagnosis methodology using the embedded fibre based on the heterodyne interferometric phase-sensitive optical time-domain reflectometry (φ-OTDR) and Hilbert demodulation is proposed. The proposed method is verified by a PD experiment with preset defects in 220 kV submarine cables under DC voltage. The results show that the PD can be detected by fibre using the proposed method. Among the three types of PD generated in preset defects in 220 kV submarine cables under DC voltage
the inception voltage of corona discharge
internal airgap discharge and surface discharge is 18
14 and 14 kV
respectively. The peak value of the phase difference in corona discharge is the smallest
and the peak value of the phase difference in surface discharge is close to that in internal airgap discharge. A recommended parameter configuration is provided through statistical analysis
where a modulation frequency of 10 kHz and a pulse width of 100 ns achieve a 10% detection probability at 2.25 km fibre length and 10 m spatial resolution.
Partial discharge (PD) is the indicator of the insulation defect in cables. However
the pulse current method
which is widely adopted in land cables
cannot obtain PD signals of high-voltage direct current (HVDC) submarine cables due to attenuation and installation position. To detect the PD of the HVDC submarine cable
a PD vibration diagnosis methodology using the embedded fibre based on the heterodyne interferometric phase-sensitive optical time-domain reflectometry (φ-OTDR) and Hilbert demodulation is proposed. The proposed method is verified by a PD experiment with preset defects in 220 kV submarine cables under DC voltage. The results show that the PD can be detected by fibre using the proposed method. Among the three types of PD generated in preset defects in 220 kV submarine cables under DC voltage
the inception voltage of corona discharge
internal airgap discharge and surface discharge is 18
14 and 14 kV
respectively. The peak value of the phase difference in corona discharge is the smallest
and the peak value of the phase difference in surface discharge is close to that in internal airgap discharge. A recommended parameter configuration is provided through statistical analysis
where a modulation frequency of 10 kHz and a pulse width of 100 ns achieve a 10% detection probability at 2.25 km fibre length and 10 m spatial resolution.