Ming Wu, Yiming Zhao, Yunfei Zhang, et al. Developing Implantable High-Sensitivity Piezoelectric Thin-Film Sensor to Monitor Partial Discharge of Generator Stator Windings[J]. High Voltage, 2026, 11(2).
DOI:
Ming Wu, Yiming Zhao, Yunfei Zhang, et al. Developing Implantable High-Sensitivity Piezoelectric Thin-Film Sensor to Monitor Partial Discharge of Generator Stator Windings[J]. High Voltage, 2026, 11(2).DOI: 10.1049/hve2.70108.
Developing Implantable High-Sensitivity Piezoelectric Thin-Film Sensor to Monitor Partial Discharge of Generator Stator Windings
摘要
Insulation failures resulting from partial discharges (PD) in generator stator windings represent a leading cause of generator breakdowns. Conventional acoustic emission sensors for detecting PD ultrasonic signals are typically made from bulky piezoelectric materials and are restricted to external placement on the generator. Their distant placement from the PD source limits sensitivity. This study presents an implantable piezoelectric thin-film ultrasonic sensor designed for high-sensitivity
real-time monitoring of PD-induced ultrasonic signals within generator stator windings. The sensor features a Pb(Zr0.52
Ti0.48)O3 thin film with an enlarged electrode area to improve sensitivity. In tests using a pencil-lead break on a polyethylene plate as the ultrasonic source
the implantable sensor exhibited a higher peak-to-peak signal than a commercial broadband sensor and nearly twice that of a commercial polyvinylidene fluoride (PVDF) sensor. The implantable sensor demonstrated an upper frequency detection limit of 80 kHz for pencil-break signals
compared to 30 kHz for both the broadband and PVDF sensors. Full-scale generator experiments validated the sensor’s high-fidelity detection of PD signals
emphasising its potential to enhance insulation condition monitoring in power systems.
Abstract
Insulation failures resulting from partial discharges (PD) in generator stator windings represent a leading cause of generator breakdowns. Conventional acoustic emission sensors for detecting PD ultrasonic signals are typically made from bulky piezoelectric materials and are restricted to external placement on the generator. Their distant placement from the PD source limits sensitivity. This study presents an implantable piezoelectric thin-film ultrasonic sensor designed for high-sensitivity
real-time monitoring of PD-induced ultrasonic signals within generator stator windings. The sensor features a Pb(Zr0.52
Ti0.48)O3 thin film with an enlarged electrode area to improve sensitivity. In tests using a pencil-lead break on a polyethylene plate as the ultrasonic source
the implantable sensor exhibited a higher peak-to-peak signal than a commercial broadband sensor and nearly twice that of a commercial polyvinylidene fluoride (PVDF) sensor. The implantable sensor demonstrated an upper frequency detection limit of 80 kHz for pencil-break signals
compared to 30 kHz for both the broadband and PVDF sensors. Full-scale generator experiments validated the sensor’s high-fidelity detection of PD signals
emphasising its potential to enhance insulation condition monitoring in power systems.
800 kV Fast Circuit Breaker: Mechanical Coupling Modelling, Buffer Design and Development
Enhancing Hydrophobic Stability of Silicone Rubber Insulators Under High-Voltage Direct Current Stress Through Optimised Nano-Fumed Silica Surface Area: A Dynamic Drop Test Study
Residual Life Assessment of Oil-Immersed Insulating Paper by FTIR Feature Interpretability Evolution
Analysis of the Anti High-Altitude Electromagnetic Pulse Interference Ability of Relay Protection Devices
DC Side Impedance Modelling of an Actual Line Commutated Converter High Voltage Direct Current System and DC Resonance Characteristics