A novel GIS breakdown location method based on natural frequency of transient voltage
摘要
Abstract
During on-site withstand voltage tests of gas-insulated switchgears (GIS)
once a breakdown occurs
it is hard to locate the breakdown position due to the intricate branch structures and minimal breakdown energy. The existing methods may require the placement of a large number of sensors with unsatisfactory accuracy
which adversely affects the process of inspecting and repairing
as well as the subsequent tests. To address this issue
this paper introduces a novel GIS breakdown location method. This method is predicated on the natural frequency of the transient voltage caused by the breakdown. The relationship between the breakdown position and the natural frequency is first derived
which is referred to as the location equation. Then
the natural frequency characteristics are discussed from both mathematical and energy perspectives. Based on these characteristics
the location method is proposed that utilises the location equation and the frequencies at two measurement points. The results of the laboratory experiments demonstrate the accuracy of the method and certain advantages over the ultrasonic method. Further
the effectiveness of the method in GIS and gas-insulated transmission lines (GIL) with complex structures and high voltage levels is also confirmed by simulation cases and field experimental data.