Severity assessment of local ageing defects in cross-linked polyethylene cables based on the high-voltage frequency domain spectroscopy non-linearity and its sensitivity analysis
High VoltageVol. 10, Issue 2, (2025)
作者机构:
1. School of Electrical Engineering, Beijing Jiaotong University,Beijing,China
2. State Key Laboratory of Alternate Electrical Power System With Renewable Energy Sources, North China Electric Power University,Beijing,China
3. State Grid Qinhuangdao Power Supply Company,Qinhuangdao,China
4. State Grid Shandong Electric Power Company Heze Power Supply Company,Heze,China
Haoyue Wang, Meng Li, Yiyi Zhu, et al. Severity assessment of local ageing defects in cross-linked polyethylene cables based on the high-voltage frequency domain spectroscopy non-linearity and its sensitivity analysis[J]. High Voltage, 2025, 10(2).
DOI:
Haoyue Wang, Meng Li, Yiyi Zhu, et al. Severity assessment of local ageing defects in cross-linked polyethylene cables based on the high-voltage frequency domain spectroscopy non-linearity and its sensitivity analysis[J]. High Voltage, 2025, 10(2). DOI: 10.1049/hve2.12518.
Severity assessment of local ageing defects in cross-linked polyethylene cables based on the high-voltage frequency domain spectroscopy non-linearity and its sensitivity analysis
摘要
Local ageing defects are the main causes of cross-linked polyethylene (XLPE) power cable faults. This research aims at assessing the severity level of typical cable local ageing defects based on the high-voltage frequency domain spectroscopy (FDS) non-linearity. Experimentally
typical XLPE cables ageing defect conditions are simulated
with different ageing types
degrees
and local proportions. Then
the high-voltage FDS detection is conducted and the results have been analysed. It has been found that the high-voltage FDS non-linearity is only related to the detection voltage and ageing degree. Especially
it is more sensitive to changes in the ageing severity. Thus
the local ageing defect severity assessment method based on non-linearity has been established. Additionally
the sensitivity has been compared between two diagnostic evaluation methods: the high-voltage FDS and the widely used very-low frequency method (VLF
0.1 Hz). It can be concluded from the comparison result that the proposed assessment method has higher sensitivity than that of the traditional methods. Finally
the effectiveness of the proposed method for evaluating the on-site long cables has been validated. The result demonstrates that the proposed method can assess on-site long cables and has the potential to be formed as quantitative standards.
Abstract
Local ageing defects are the main causes of cross-linked polyethylene (XLPE) power cable faults. This research aims at assessing the severity level of typical cable local ageing defects based on the high-voltage frequency domain spectroscopy (FDS) non-linearity. Experimentally
typical XLPE cables ageing defect conditions are simulated
with different ageing types
degrees
and local proportions. Then
the high-voltage FDS detection is conducted and the results have been analysed. It has been found that the high-voltage FDS non-linearity is only related to the detection voltage and ageing degree. Especially
it is more sensitive to changes in the ageing severity. Thus
the local ageing defect severity assessment method based on non-linearity has been established. Additionally
the sensitivity has been compared between two diagnostic evaluation methods: the high-voltage FDS and the widely used very-low frequency method (VLF
0.1 Hz). It can be concluded from the comparison result that the proposed assessment method has higher sensitivity than that of the traditional methods. Finally
the effectiveness of the proposed method for evaluating the on-site long cables has been validated. The result demonstrates that the proposed method can assess on-site long cables and has the potential to be formed as quantitative standards.