Zhipeng Yu, Yongpeng Xu, Guoliang Qi, et al. Dynamic characteristics of sub-cycle incipient faults in medium-voltage cable joints[J]. Global Energy Interconnection, 2025, 8(6).
DOI:
Zhipeng Yu, Yongpeng Xu, Guoliang Qi, et al. Dynamic characteristics of sub-cycle incipient faults in medium-voltage cable joints[J]. Global Energy Interconnection, 2025, 8(6). DOI: 10.1016/j.gloei.2025.05.009.
Dynamic characteristics of sub-cycle incipient faults in medium-voltage cable joints
摘要
Abstract
Permanent faults in medium-voltage cable joints significantly impact the reliability of distribution networks.Radial breakdowns caused by water ingress often lead to several self-extinguishing arc discharges—referred to as incipient faults—before developing into permanent faults.Effective monitoring of incipient faults can help reduce outage costs associated with permanent faults.However
the specific fault scenarios of incipient faults remain insufficiently understood.To address this gap
this study designed a simulation experiment replicating incipient fault conditions in medium-voltage cable joints under humid environments
based on actual operating scenarios.The experiment compared the insulation strength required to trigger incipient faults and examined both non-electrical fault characteristics
such as insulation damage and arc flame intensity
and electrical characteristics
such as fault current and impedance.Experimental observations show that
in cable joints
gaps without accumulated water retain sufficient insulation strength to prevent breakdown.However
the infiltration of accumulated water shortens the effective insulation path
thereby lowering the breakdown threshold.The peak current of an incipient fault can range from hundreds to thousands of amperes
with a duration of approximately 1/8 to 1/4 of a power–frequency cycle.During incipient faults
arc burning on the pore wall leaves conductive traces
which progressively reduce the insulation strength of the surrounding environment.As these traces accumulate over multiple events
the likelihood of breakdown increases
ultimately resulting in a permanent fault.Permanent faults are characterized by intense
sustained arc discharges that persist over a macroscopic time scale and exhibit flatshoulder waveforms within individual cycles
with discharge intensity increasing progressively over time.