Consideration of the influence of supports in modeling the electromagnetic fields of 25 kV traction networks under emergency conditions
Global Energy InterconnectionVol. 7, Issue 4, Pages: 528-540(2024)
作者机构:
1. Department of Hydropower and Renewable Energy, National Research University, Moscow Power Engineering Institute,Moscow,Russia,11250
2. Department of Power Supply and Electrical Engineering, Irkutsk National Research Technical University,Irkutsk,Russia,664074
3. Department of Transport Electric Power, Irkutsk State Transport University,Irkutsk,Russia,664074
4. Department of Research on the Relationship Between Energy and the Economy, Energy Research Institute of the Russian Academy of Sciences,Moscow,Russia,117186
Konstantin Suslov, Andrey Kryukov, Ekaterina Voronina, et al. Consideration of the influence of supports in modeling the electromagnetic fields of 25 kV traction networks under emergency conditions[J]. Global Energy Interconnection, 2024, 7(4): 528-540.
DOI:
Konstantin Suslov, Andrey Kryukov, Ekaterina Voronina, et al. Consideration of the influence of supports in modeling the electromagnetic fields of 25 kV traction networks under emergency conditions[J]. Global Energy Interconnection, 2024, 7(4): 528-540.DOI: 10.1016/j.gloei.2024.08.004.
Consideration of the influence of supports in modeling the electromagnetic fields of 25 kV traction networks under emergency conditions
Single-phase 25 kV traction networks of electrified alternating current (AC) railways create electromagnetic fields (EMFs) with significant levels of intensity. The most intense magnetic fields occur when short circuits exist between the contact wire and rails or ground. Despite the short duration of exposure
they can adversely affect electronic devices and induce significant voltages in adjacent power lines
which is dangerous for operating personnel. Although numerous investigations have focused on modeling the EMF of traction networks and power lines
the challenge of determining the three-dimensional electromagnetic fields near metal supports during the flow of a short-circuit current through them is yet to be resolved. In this case
the field has a complex spatial structure that significantly complicates the calculations of intensities. This study proposes a methodology
algorithms
software
and digital models for determining the EMF in the described emergency scenarios. During the modeling process
the objects being studied were represented by segments of thin wires to analyze the distribution of the electric charge and calculate the intensities of the electric and magnetic fields. This approach was implemented in the Fazonord software
and the modeling results show a substantial increase in EMF levels close to the support
with a noticeable decrease in the levels as the distance from it increases. The procedure implemented in the commercial software Fazonord is universal and can be used to determine electromagnetic fields at any electrical power facility that includes live parts of limited length. Based on the proposed procedure
the EMF near the supports of overhead power lines and traction networks of various designs could be determined
the EMF levels at substations can be calculated
and the influence of metal structures located near traction networks
Analysis of the impact of grid-forming doubly-fed induction generator parameter on transient stability and small-signal stability
EV${7*7}AL
Negative electricity prices in electricity markets: causes, impacts,and response strategies
Multi-scenario coordinated operation strategy of battery-hydrogen hybrid energy storage system for pure photovoltaic VSC-HVDC converter station