Jianrui Li, Yongli Li, Yonghuan Wang, et al. Single-phase-to-ground fault protection based on zero-sequence current ratio coefficient for low-resistance grounding distribution network[J]. Global Energy Interconnection, 2021, 4(6): 564-575.
DOI:
Jianrui Li, Yongli Li, Yonghuan Wang, et al. Single-phase-to-ground fault protection based on zero-sequence current ratio coefficient for low-resistance grounding distribution network[J]. Global Energy Interconnection, 2021, 4(6): 564-575.DOI: 10.1016/j.gloei.2022.01.001.
Single-phase-to-ground fault protection based on zero-sequence current ratio coefficient for low-resistance grounding distribution network
摘要
Abstract
Definite-time zero-sequence over-current protection is presently used in systems whose neutral point is grounded by a low resistance (low-resistance grounding systems). These systems frequently malfunction owing to their high settings of the action value when a high-impedance grounding fault occurs. In this study
the relationship between the zero-sequence currents of each feeder and the neutral branch was analyzed. Then
a grounding protection method was proposed on the basis of the zero-sequence current ratio coefficient. It is defined as the ratio of the zero-sequence current of the feeder to that of the neutral branch. Nonetheless
both zero-sequence voltage and zero-sequence current are affected by the transition resistance
The influence of transition resistance can be eliminated by calculating this coefficient. Therefore
a method based on the zero-sequence current ratio coefficient was proposed considering the significant difference between the faulty feeder and healthy feeder. Furthermore
unbalanced current can be prevented by setting the starting current. PSCAD simulation results reveal that the proposed method shows high reliability and sensitivity when a high-resistance grounding fault occurs.
Multi-scenario coordinated operation strategy of battery-hydrogen hybrid energy storage system for pure photovoltaic VSC-HVDC converter station
Analysis of the impact of grid-forming doubly-fed induction generator parameter on transient stability and small-signal stability
Research on benefit coordination mechanism in renewable energy multi-energy complementary systems
Forecasting the average daily and during the hours of maximum electric load based on the data of the average monthly electricity consumption with single and other energy sources
Momentum vectorized adaptive DDPG-based PSC mitigator design for hybrid PV-TEG systems with auxiliary battery participation