The fully enclosed feature of the GIS bus makes it impossible to directly measure the temperature of its internal conductor.To solve this problem
a GIS bus temperature deduction method based on finite element analysis is proposed
this method uses directly measurable GIS bus shell temperature
load current
ambient temperature and other parameters to derive conductor temperature.First
combined with GIS bus parameters
thermal parameters and boundary conditions
the COMSOL finite element analysis software is used to conduct electromagnetic-fluid-temperature field coupling simulation to solve the GIS bus temperature under different ambient temperature and load current conditions to obtain sample data.Finally
use sample data for training to establish a GIS bus temperature deduction model.The analysis results show that the temperature of the GIS bus conductor can be quickly obtained through the proposed temperature deduction method
which is of great significance for the safe operation of the GIS bus and the prevention of accidents.