The cause for one accident in Xichang power grid is analyzed
and it shows that misoperation of protective gas neutral point is the result of the unsuitable setting of neutral point protective gap of transformer.It proposes that when setting the protective gap of the neutral point of transformer
it is not suitable to set one certain value
it is necessary to consider the actual height above sea level and the impact of dirtiness on the operating environment