MA Shi-ying~1, HUANG Jing~2, QU Gui-yin~1. Study on current sharing technology of bus fed static excitation system of synchronous generator with redundant design[J]. 2006, (5): 5-8.
MA Shi-ying~1, HUANG Jing~2, QU Gui-yin~1. Study on current sharing technology of bus fed static excitation system of synchronous generator with redundant design[J]. 2006, (5): 5-8.DOI:
Study on current sharing technology of bus fed static excitation system of synchronous generator with redundant design
Current unbalance is a common problem in bus fed static excitation system of synchronous generator with redundant design.The factors led to current unbalance
such as dispersion of positive-direction characteristic of rectifier
difference of inductance in source circuit
difference of trigger characteristic of rectifier
difference of touch resistance when rectifier and fast-fuse are installed
difference of wiring of rectifier
and difference of bus resistance
were analyzed in this paper. The improvements of current sharing
such as careful choosing rectifier
improving structure of the device
adding balance reactor
and dynamically balancing current
were presented and the advantage of dynamic current sharing was analyzed in this paper.