YIN Jian-guo1, JIANG Zheng-long2, WANG Cheng2, et al. Analysis and prevention of the lightning trip on 110kV Baoqingyang line[J]. 2008, 28(6): 26-30.DOI:
Analysis and prevention of the lightning trip on 110kV Baoqingyang line
摘要
对湖南邵阳电业局宝青洋线路雷击跳闸率进行了计算
并结合现场调查分析认为雷击跳闸率高的原因主要受到地形、塔型、雷电流释放通道及绝缘配置的影响
在此基础上对杆塔接地网和雷电流泄放通道进行了改造
在易遭雷击的杆塔塔顶安装多根发散状的短避雷针等措施来减少雷击闪络的概率
防雷改造后到目前4年多未发生雷击跳闸。
Abstract
According to calculating the lightning trip rate of 110kV Baoqingyang line and practical investigation
it is considered that the terrain
the tower
the thunder electric current release channel and the external insulation disposition were responsible for the high lightning trip rate.The tower grounding grid and thunder electric current release channel were then modified.Multiple short-root divergence lightning rods were installed on the top of towers easily suffered from lightning to reduce the probability of flashover.After lightning prevention modification
the transmission line has had no lightning trip for four years.