Average lightning failure trip ratio of ±500kV Jiang-Cheng HVDC is 0.370 time per 100km·year
in which 84.2% happened at positive pole.Based on databases of Hunan lightning location system and sampling data from Jiang-Cheng fault tower
lightning movement parameters of 500kV Jiang-Cheng transmission line corridor were statistically analyzed and the results indicated that it is appropriate to set the length of side at 20km.Lightning densities of line corridor can vary much
but lightning current magnitude distributions are similar.Middle current of lightning magnitude is between 19.5kA and 24.6kA.Calculation results from rule method
multi-surge impedance method
and circuit method showed that shielding failure is the main cause for Jiang-Cheng HVDC lightning failure.