CHEN Hou-tao, LIU Wu-lin, LIU Fu-ping, et al. Study on superheated steam temperature control in 660 MW supercritical power unit[J]. 2013, 33(4): 1-5.DOI:
Study on superheated steam temperature control in 660 MW supercritical power unit
According to the characteristics of superheated steam temperature in supercritical once-through boiler
a steam temperature control system is designed based on controlled object properties.In this system
succesful control of superheated steam temperature is achieved by combining the fuel water ratio control based on intermediate point enthalpy value and two loops spray desuperheating regulation.Engineering application indicates that the excellent regulation quality of steam temperature is obtained whether in steady state or in variable load condition.