国网湖南省电力公司电力科学研究院
Published:2016
移动端阅览
[1]黄福勇,孙利朋,徐波,段肖力,吴水锋.GIS套管放电性缺陷带电检测分析[J].湖南电力,2016,36(02):69-71.
HUANG Fuyong, SUN Lipeng, XU Bo, et al. Analysis of on-line detection of GIS bushing discharge fault[J]. 2016, 36(2): 69-71.
[1]黄福勇,孙利朋,徐波,段肖力,吴水锋.GIS套管放电性缺陷带电检测分析[J].湖南电力,2016,36(02):69-71. DOI:
HUANG Fuyong, SUN Lipeng, XU Bo, et al. Analysis of on-line detection of GIS bushing discharge fault[J]. 2016, 36(2): 69-71. DOI:
本文介绍了GIS套管常见的放电性缺陷
以及带电检测方法和原理
分析了放电性缺陷产生的原因。结合一起GIS套管外部放电性缺陷
利用红外测温、超声波法和特高频法进行了综合诊断
并对缺陷部位、缺陷原因和治理措施进行了分析。
This paper introduces the common discharge defects of gas insulated switchgear( GIS) bushing
on-line detection methods and principles
and analyzes the causes of discharge defects. According to a GIS bushing external discharge defect
this paper uses comprehensive diagnosis of infrared
ultrasonic and ultra high frequency( UHF)
and analyzes defective parts
the causes of defects and preventive methods.