PENG Ping, ZHOU Xinjun, YOU Kai. Influence of core ungrounding on dielectric loss and capacitance of transformer winding[J]. 2016, 36(3): 47-49+53.DOI:
Influence of core ungrounding on dielectric loss and capacitance of transformer winding
摘要
从试验原理和变压器内部结构出发
采用等效电容的方法
对一起220kV变压器绕组介质损耗因素和电容量试验数据异常的案例进行分析
分析了铁芯不接地导致变压器绕组介质损耗因素和电容量测量结果异常的原因。
Abstract
Dielectric loss and capacitance measuring is an important method to check the condition of transformer insulation.The capacitance is also an important auxiliary parameters to judge the winding deformation. From the test principle and the internal structure of transformer
equivalent capacitance was used to analyze a case of abnormal dielectric loss and capacitance for a 220kV transformer
and the reason of abnormal dielectric loss and capatitance date causell by core ungrounling is analyzed.