WANG Feifei. Feasibility study and practice of checking the polarity of differential protection by using the inrush current[J]. 2016, 36(6): 26-29.DOI:
Feasibility study and practice of checking the polarity of differential protection by using the inrush current
摘要
以清蓄电厂为例介绍利用主变压器充电时的励磁涌流校核差动保护极性的可行性分析和实践过程
该方法克服电厂负荷低的困难
利用励磁涌流电流导相偏置的特点开展带负荷检查
具有实际工程意义
可供新并网厂站校核差动保护极性作参考。
Abstract
Taking Qingyuan power plant as an example
the feasibility analysis and practice are introduced using the main transformer charging excitation inrush current to check the polarity. The methed can overcome the difficuties of low load and check polarity of the differential protectin with load by the characteristics of inrush current pilot bias. The result illustrate this method has engineering significance
and it can be a reference for new power plant to check the polarity of the differential protection.