A severe scaling problem of a 600MW subcritical unit’s condenser stainless steel tubes was discovered during the overhaul.The appearance
mass and composition of the scale sample were detected.The possible reasons of the quality of raw water
the operation control of circulating water
the commission of rubber balls and the quality of scale inhibitor were analyzed.The investigation showed that the severe scaling was caused by scaling sensitive raw water
the bad operations on the scale inhibitor and the un-normal cleaning mode of rubber balls.