CHAO Yafeng, LIU Ming, YUE Yishi, et al. Analysis and Countermeasures of Prevent Ice-Melting Flashover for Hunan Power Grid Transmission Lines[J]. 2017, 37(3): 30-33.
CHAO Yafeng, LIU Ming, YUE Yishi, et al. Analysis and Countermeasures of Prevent Ice-Melting Flashover for Hunan Power Grid Transmission Lines[J]. 2017, 37(3): 30-33.DOI:
Analysis and Countermeasures of Prevent Ice-Melting Flashover for Hunan Power Grid Transmission Lines
The outdoor insulation of the transmission lines of Hunan Power Grid is checked in this paper
the result displays that there are 66. 05% of 220kV transmission lines can not meet the demand of prevent ice-melting flashover
and for 500kV transmission lines
the percentage is 36. 17%. And in the superposition region of heavy icing area and e class pollution area
there are 1. 03% of towers can not meet the demand of prevent ice-melting flashover for 220kV transmission lines
and for 500kV transmission lines
the percentage is 0. 45%. Self-defect and insufficient of anti-icing improvement are the primary causes of the poor prevent ice-melting flashover capacity for the overhead transmission lines. The strategy of prevent ice-melting flashover by improving forecast accuracy ment
reinforcing the manager of ice condition observation
classifying and focusing on the poor prevent ice-melting flashover capacity facility are proposed. And the operation and improvement advice for prevent ice-melting flashover is also proposed in the paper.