QIN Jiayuan, LIU Yun, SUN Lipeng. Diagnosis and Analysis of 110 kV GIS Cable Terminal Energized Test[J]. 2019, 39(2): 30-32+52.DOI:
Diagnosis and Analysis of 110 kV GIS Cable Terminal Energized Test
摘要
采取特高频、超声波局部放电等多种带电检测方式
可以有效检测GIS设备潜伏性局部放电缺陷。针对某变电站一起110 kV GIS电缆终端局部放电缺陷
采用特高频定位检测查找缺陷部位
综合特高频、超声波局部放电及高频电流法定性分析缺陷类型
最后通过停电解体验证了GIS终端存在气隙放电缺陷。
Abstract
Using UHF and ultrasonic partial discharge can effectively detect the latent defects partial discharge of GIS equipment. In view of a partial discharge defect of a 110 kV substation GIS cable terminal
using UHF positioning to find defect site
combined with UHF
ultrasonic partial discharge and high-frequency current method
the gas gap discharge defect of GIS terminal is verified by power cut.