ZENG Huarong, MA Xiaohong, XU Kui, et al. Measurement Method and Applicability Analysis of Transmission Line Tower Power Frequency Grounding Resistance in Mountainous Area[J]. 2019, 39(3): 66-69.
ZENG Huarong, MA Xiaohong, XU Kui, et al. Measurement Method and Applicability Analysis of Transmission Line Tower Power Frequency Grounding Resistance in Mountainous Area[J]. 2019, 39(3): 66-69.DOI:
Measurement Method and Applicability Analysis of Transmission Line Tower Power Frequency Grounding Resistance in Mountainous Area
摘要
在贵州的山区条件下
用传统的三极法测量输电线路杆塔的工频接地电阻存在很大的操作难度
通过对比测量杆塔工频接地电阻的几种方法
包括三极法(摇表法)、钳表法和回路法等
比较了不同接地电阻测量方法下测得工频接地电阻的差异
从原理上分析了实际测量中产生误差的原因
并通过三极法和回路法实际测量220 k V台白线中的4基杆塔
对比了回路法和三极法的差异
建议了回路法测量杆塔工频接地电阻的使用要求
对实际工作中测量杆塔工频接地电阻有重要的指导意义。
Abstract
In the mountainous area of Guizhou Province
it is difficult to measure the power frequency grounding resistance of transmission line poles and towers by the traditional three electrode method. This paper compares several methods of measuring tower grounding resistance
including three electrode method
clamp meter method and looping method
and compares the difference of grounding resistance measured under different grounding resistance measurement methods
analyzes the error reason from actual measurement. Four towers in 220 k V Taibai line are measured by three electrode method and loop method to compare their difference. The requirements of using loop method to measure grounding resistance are specified and it has important guiding significance for measuring grounding resistance in practical work.