Optimal Configuration Method of SVG Based on Transient Voltage Recovery Characteristics
this paper studies the influence of the position of SVG on the transient voltage recovery characteristics based on the time domain simulation results of PSASP. The simulation results show that the distributed SVG configuration in east Hunan and south Hunan has better voltage support effect due to the load distribution characteristics of Hunan power grid. In addition
the simulation results also show that SVG which deployed on the low voltage side of 220 kV substation has better transient voltage recovery characteristics than that of 500 kV substation.