Optimization of Control Strategy for Load Rejection to Ensure Auxiliary Power Consumption in a Hydropower Plant
摘要
针对某水电厂甩负荷后会出现V/Hz限制保护动作
启动紧急事故停机
无法满足机组保厂用电的问题
提出了快速响应和超前预判相结合的方法
利用PID控制系统原理
对开机和甩负荷逻辑进行了改进
使频率低值在响应速度方面理论上得以提高。以优化后的甩负荷控制系统为内容做试验
试验结果避免了V/Hz限制保护动作
所提出的方法对抑制频率超调现象具有普遍适用性。
Abstract
In view of the problem that a hydro-power plant will have V/Hz limiting protection action and start emergency shutdown after load rejection and cannot meet the demand for auxiliary power protection of the unit
a method combining fast response and advanced pre-judgment is proposed. The PID control system principle is used to improve the startup and load rejection logic
so that the low frequency can be theoretically improved in response speed. Taking the optimized load rejection control system as the test content
the V/Hz limiting protection action is avoided