ZHANG Tailei, SHI Hui, WANG Ding. Analysis on Condenser Leading-phase Operation Influence at Valley Load Period of Hunan Power Grid[J]. 2020, 40(5): 30-34.
ZHANG Tailei, SHI Hui, WANG Ding. Analysis on Condenser Leading-phase Operation Influence at Valley Load Period of Hunan Power Grid[J]. 2020, 40(5): 30-34.DOI:
Analysis on Condenser Leading-phase Operation Influence at Valley Load Period of Hunan Power Grid
摘要
在湖南电网低谷负荷水平条件下
研究韶山换流站调相机对电网运行的影响。仿真结果表明
调相机参与地区电压控制时
高电压等级静态调压比低电压等级的效果更好。考虑故障方式时
调相机对电压稳定的影响与进相深度有关。调相机进相运行可以提升系统无功储备水平
通过置换负荷中心火电机组开机
有助于缓解低谷调峰压力。
Abstract
The influence of condenser in Shaoshan converter station on Hunan power grid at valley load period is studied in this paper. The simulation results show that the high voltage level is better regulated than the low voltage level when the condenser participates in the regional voltage control. When fault mode is considered
the effect of condenser on voltage stability is related to the level of phase-lead operation. The leading-phase operation of condenser can improve the system reactive power reserve level and relieve the pressure of peak load regulation at valley period by replacing load center thermal.