ZHAO Bushi, HE Rufei, BI Zhiwei, et al. Risk Analysis of Switch Position Signal Using Extended Contacts for Pumped Storage Unit Protection[J]. 2020, 40(5): 51-54.
ZHAO Bushi, HE Rufei, BI Zhiwei, et al. Risk Analysis of Switch Position Signal Using Extended Contacts for Pumped Storage Unit Protection[J]. 2020, 40(5): 51-54.DOI:
Risk Analysis of Switch Position Signal Using Extended Contacts for Pumped Storage Unit Protection
摘要
抽水蓄能机组及变压器保护需要采集开关位置信号进行工况判别
由于开关本体的位置辅助接点数量有限
往往需要接点扩展之后再供保护使用。以主变差动保护用的GCB分位接点信号为例
通过对开关行程、动作时序、保护动作逻辑的分析
研究了开关位置信号采用扩展接点对保护动作行为造成的影响
提出了由此产生的保护误动风险
并给出防范此问题的建议。
Abstract
The pumped storage unit and the transformer protection need to collect the switch position signal for the working condition discrimination. Because the position of the switch body is limited
it is often necessary to expand the contact point for protection. Taking the GCB grading contact for main transformer differential protection as an example
through the analysis of the switching stroke
the action sequence
the protection action logic and the influence of the extended position on the protection action behavior of the switch position signal is studied. The risk of protection misoperation is put forward
and some suggestions about preventing this problem are given.