Analysis of Influence of 500 kV Current Limiter Access on Power Flow Distribution in Guangdong Power Grid
|更新时间:2025-11-18
|
Analysis of Influence of 500 kV Current Limiter Access on Power Flow Distribution in Guangdong Power Grid
Vol. 41, Issue 3, Pages: 58-61+68(2021)
作者机构:
广州电力设计院有限公司
作者简介:
基金信息:
DOI:
CLC:TM471
Published:2021
稿件说明:
移动端阅览
YANG Fan, ZHANG Xu, YE Qige. Analysis of Influence of 500 kV Current Limiter Access on Power Flow Distribution in Guangdong Power Grid[J]. 2021, 41(3): 58-61+68.
DOI:
YANG Fan, ZHANG Xu, YE Qige. Analysis of Influence of 500 kV Current Limiter Access on Power Flow Distribution in Guangdong Power Grid[J]. 2021, 41(3): 58-61+68.DOI:
Analysis of Influence of 500 kV Current Limiter Access on Power Flow Distribution in Guangdong Power Grid
The series current limiting reactor can effectively limit the short-circuit current of 500 kV voltage level
but it will affect the power flow distribution and transient stability of the system when it is connected to the system. The power flow change and the maximum power angle difference change under the fault scenario of 500 kV/90 kA current limiter based on high coupling reactance type are studied by using BPA simulation software in Guangnan railway station. The results show that when the coupling coefficient of 500 kV current limiter is 0.97
the external leakage reactance is small
which will not affect the node voltage in normal operation of the system.However
the leakage reactance of the external performance may still cause the increase of reactive power loss. With the decrease of the coupling coefficient
the leakage reactance of the current limiter increases
which will pull down the normal working voltage of the node and increase the reactive power loss.