LI Shaobin, PENG Yong, TANG Wenbo, et al. Analysis on Flange Root Crack of GIS Terminal[J]. 2021, 41(4): 87-90.
DOI:
LI Shaobin, PENG Yong, TANG Wenbo, et al. Analysis on Flange Root Crack of GIS Terminal[J]. 2021, 41(4): 87-90.DOI:
Analysis on Flange Root Crack of GIS Terminal
摘要
分析了一起110 kV GIS终端环氧套管根部法兰面产生异常裂纹的故障
结果表明
当GIS终端顶部导电套与GIS仓导电杆的装配精度不足时
导电杆可能会在GIS终端环氧套管上产生形变应力
最终破坏环氧套管
根部法兰处形成的裂纹导致气体泄漏引发故障
最后提出了防止GIS发生漏气故障的建议。
Abstract
This paper analyzes a failure case of abnormal crack on flange root of epoxy bushing.When the assembling accuracy of the conductive sleeve on the top of the GIS terminal and the conductive bar of the GIS warehouse is not enough
the conductive bar may cause deformation stress on the Epoxy Sleeve of the GIS terminal
and finally destroy the epoxy sleeve.Cracks on epoxy bushing of GIS terminal cause failure and eventually leading a gas leakage. At the end of the article