In order to further optimize the output current harmonic suppression effect of photovoltaic grid-connected inverters
this paper proposes a composite control strategy for the output current of LCL photovoltaic grid-connected inverters. This strategy combines proportional complex integral(PCI) control and repetitive control(RC)
draws a composite control block diagram
introduces a transfer function
and designs PCI and RC control parameters. It is concluded that the compound control can effectively suppress the current harmonics
save the control cost of the grid-connected system
and achieve the purpose of reducing the steady-state error of the fundamental frequency. By building the MATLAB/Simulink simulation platform and establishing the LCL type photovoltaic grid-connected inverter model
the comparison of the simulation results shows that compared with the PI+RC control strategy
the total harmonic distortion rate of the grid-connected current is reduced by 25.77%
significantly improving the quality of grid-connected current.