Field Test and Simulation Analysis of Overvoltage Suppression Capability for 10 kV Overvoltage Absorber and Arrester
|更新时间:2025-11-18
|
Field Test and Simulation Analysis of Overvoltage Suppression Capability for 10 kV Overvoltage Absorber and Arrester
Vol. 41, Issue 5, Pages: 7-13+21(2021)
作者机构:
1. 国网湖南省电力有限公司电力科学研究院
2. 国网湖南省电力有限公司
3. 湖南长高森源电力设备有限公司
作者简介:
基金信息:
DOI:
CLC:TM862
Published:2021
稿件说明:
移动端阅览
XIANG Yingzhu, LI Xin, XIAO Jing, et al. Field Test and Simulation Analysis of Overvoltage Suppression Capability for 10 kV Overvoltage Absorber and Arrester[J]. 2021, 41(5): 7-13+21.
DOI:
XIANG Yingzhu, LI Xin, XIAO Jing, et al. Field Test and Simulation Analysis of Overvoltage Suppression Capability for 10 kV Overvoltage Absorber and Arrester[J]. 2021, 41(5): 7-13+21.DOI:
Field Test and Simulation Analysis of Overvoltage Suppression Capability for 10 kV Overvoltage Absorber and Arrester
摘要
对阻容装置和避雷器的过电压抑制能力进行校核
进行变电站并联电抗器投切试验
将10 kV阻容装置和氧化锌避雷器的操作过电压防护效果对比
还对四种不同过电压防护装置配置条件下的雷电过电压响应情况进行仿真计算
得出阻容装置和氧化锌避雷器配合使用能同时降低过电压波形幅值、陡度和频率的结论。
Abstract
In this paper
the overvoltage suppression ability of the resistance-capacitance device and the arrester is checked
and the switching test of the shunt reactor in substations is carried out. The operating overvoltage protection effect of the resistance-capacitance device and the arrester is compared
the lightning overvoltage response of four different overvoltage protection devices is also simulated. It is concluded that the amplitude
steepness and frequency of the overvoltage waveform can be decreased by using the resistance-capacitance device together with metal oxide arrester.