Aiming at the system stability problems existing in large-scale grid connection of new energy
this paper analyzes the reactive power compensation capacity of DFIG units
introduces battery energy storage static synchronous compensator(STATCOM/BESS) into DFIG grid connection system
and puts forward a method to maintain the power and voltage stability of DFIG wind power grid connection system by using STATCOM/BESS. Based on the traditional STATCOM reactive power compensation
the battery energy storage is connected in parallel on its DC side
which can quickly and smoothly adjust the active power of the wind farm input and network point
support the system voltage stability
and achieve the function of peak shaving and valley leveling. By comparing the reactive power compensation capability of DFIG
STATCOM and STATCOM/Bess in case of three-phase grounding fault
the results show that the system with STATCOM/Bess has the smallest voltage drop
the fastest recovery speed and the best compensation effect.