Research on High Voltage Cable Core Temperature Prediction Based on Data Driven Model
|更新时间:2025-11-18
|
Research on High Voltage Cable Core Temperature Prediction Based on Data Driven Model
Vol. 42, Issue 2, Pages: 59-63+67(2022)
作者机构:
1. 湖南大学电气与信息工程学院
2. 国网湖南省电力有限公司电力科学研究院
3. 国网湖南省电力有限公司湘潭供电分公司
作者简介:
基金信息:
DOI:
CLC:TM75
Published:2022
稿件说明:
移动端阅览
CHEN She, WANG Juan, ZENG Zeyu, et al. Research on High Voltage Cable Core Temperature Prediction Based on Data Driven Model[J]. 2022, 42(2): 59-63+67.
DOI:
CHEN She, WANG Juan, ZENG Zeyu, et al. Research on High Voltage Cable Core Temperature Prediction Based on Data Driven Model[J]. 2022, 42(2): 59-63+67.DOI:
Research on High Voltage Cable Core Temperature Prediction Based on Data Driven Model
Temperature is one of the important physical quantities to determine the operating status of the cable
but usually only the temperature of the outer sheath can be monitored
while the temperature of the cable core cannot be directly obtained. In this study
a temperature field model of tunnel laying 110 kV cable is built
incorporating the real-time monitoring temperature of the cable outer sheath. The cable temperature distribution is thus obtained by optimizing and correcting the physical quantities such as material parameters of the cable to make the model more consistent with the real operation state. The influences of parameters such as dielectric loss factor
dielectric constant and thermal conductivity of XLPE on the physical model of cable temperature prediction are further discussed. The temperature distribution of low resistance grounding fault in cable is simulated. It was found that the difference between the fault phase cable core temperature and its outer sheath temperature was 47 ℃
and this cable core temperature can reach 250 ℃
and meanwhile
the temperature of the same circuit non-fault phase cable core also rose to more than 120 ℃
which was in severe overload state. The data-driven high voltage cable model in this paper can effectively calculate the cable core temperature
which helps to grasp the core data and working status of cable operation
so that it can lay the foundation for the final construction of the cable digital twin model.