Research on Arc Grounding Overvoltage and Suppression Measures in Distribution Network
|更新时间:2025-11-18
|
Research on Arc Grounding Overvoltage and Suppression Measures in Distribution Network
Vol. 42, Issue 2, Pages: 50-54+58(2022)
作者机构:
1. 长沙市昌远电气科技有限公司
2. 国网湖南省电力有限公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:TM862
Published:2022
稿件说明:
移动端阅览
HAI Bin, ZENG Zeyu, LI Chao, et al. Research on Arc Grounding Overvoltage and Suppression Measures in Distribution Network[J]. 2022, 42(2): 50-54+58.
DOI:
HAI Bin, ZENG Zeyu, LI Chao, et al. Research on Arc Grounding Overvoltage and Suppression Measures in Distribution Network[J]. 2022, 42(2): 50-54+58.DOI:
Research on Arc Grounding Overvoltage and Suppression Measures in Distribution Network
For the problem of overvoltage generated by single-phase arc grounding in 10 kV distribution network
three suppression methods of neutral point grounding via arc extinguishing coil
neutral point grounding via resistance and fault phase throwing grounding resistance are proposed. The arc grounding model under distribution network are built in ATP-EMTP software to simulate the voltage characteristics. The advantages and disadvantages of three methods are compared in view of the suppression effect to the arc grounding overvoltage. The results show that the mentioned three methods can effectively reduce the arc grounding overvoltage. Grounding the neutral point via the arc extinguishing coil is a more ideal method for urban distribution system due to its better effect.