National Key R D Program on Smart Grid Integrated Sensing Storage and Computing Micro Nano Sensor Devices and Key Technologies for Multi dimensional Fusion Perception of Main Substation Equipment Status 2024ZD0803400 Analysis and diagnosis of the causes of unbalanced voltage protection action in 10kV parallel capacitor devices
|更新时间:2026-10-18
|
National Key R D Program on Smart Grid Integrated Sensing Storage and Computing Micro Nano Sensor Devices and Key Technologies for Multi dimensional Fusion Perception of Main Substation Equipment Status 2024ZD0803400 Analysis and diagnosis of the causes of unbalanced voltage protection action in 10kV parallel capacitor devices
LiKun, Zhang Die. National Key R D Program on Smart Grid Integrated Sensing Storage and Computing Micro Nano Sensor Devices and Key Technologies for Multi dimensional Fusion Perception of Main Substation Equipment Status 2024ZD0803400 Analysis and diagnosis of the causes of unbalanced voltage protection action in 10kV parallel capacitor devices[J]. 2026, 29(7): 9--.
LiKun, Zhang Die. National Key R D Program on Smart Grid Integrated Sensing Storage and Computing Micro Nano Sensor Devices and Key Technologies for Multi dimensional Fusion Perception of Main Substation Equipment Status 2024ZD0803400 Analysis and diagnosis of the causes of unbalanced voltage protection action in 10kV parallel capacitor devices[J]. 2026, 29(7): 9--.DOI:
National Key R D Program on Smart Grid Integrated Sensing Storage and Computing Micro Nano Sensor Devices and Key Technologies for Multi dimensional Fusion Perception of Main Substation Equipment Status 2024ZD0803400 Analysis and diagnosis of the causes of unbalanced voltage protection action in 10kV parallel capacitor devices
The main function of parallel capacitors is to improve power factor by providing capacitive reactive power
thereby reducing losses and increasing system voltage. In response to an incident of three-phase unbalanced voltage protection action during the switching process of a 10kV parallel capacitor device
through experimental diagnosis and theoretical calculation
it is comprehensively analyzed that the protection action was caused by the lack of short circuiting between the neutral point of the on-site capacitor and the neutral point of the discharge coil. And PSCAD was used to simulate and calculate the unbalanced voltage values of capacitors and discharge coils under neutral point short circuiting and non short circuiting conditions. The simulation results under non short circuiting conditions were basically consistent with the protection recording data
reproducing the process of protection action. At the same time
it was simulated that no protection action would be caused under short circuiting conditions. Based on the simulation results
relevant conclusions and suggestions were finally given.