Influence of magnetic shield thickness on stator end leakage reactance of synchronous condenser under different operating conditions
|更新时间:2026-10-15
|
Influence of magnetic shield thickness on stator end leakage reactance of synchronous condenser under different operating conditions
Vol. 45, Issue 9, (2026)
作者机构:
1. 中城院(北京)环境科技股份有限公司,北京,100120
2. 华北电力大学电气与电子工程学院,北京,102206
作者简介:
基金信息:
DOI:
CLC:TM342
Published:2026
稿件说明:
移动端阅览
SONG Meihong, XU Guorui. Influence of magnetic shield thickness on stator end leakage reactance of synchronous condenser under different operating conditions[J]. 2026, 45(9).
DOI:
SONG Meihong, XU Guorui. Influence of magnetic shield thickness on stator end leakage reactance of synchronous condenser under different operating conditions[J]. 2026, 45(9).DOI:
Influence of magnetic shield thickness on stator end leakage reactance of synchronous condenser under different operating conditions
The stator end magnetic shield of the synchronous condenser (SC) can reduce the losses of the end core and structural components
but it also changes the permeability of the end magnetic circuit and the stator end leakage reactance
further affecting the transient reactive power characteristics of the SC. In order to study the influence of the magnetic shield on the leakage magnetic field and leakage reactance in the stator end region
the three-dimensional end electromagnetic field model of the SC is established. The distribution of magnetic flux density and energy density in the stator end region under different magnetic shield thicknesses is calculated
and the variation law of the stator leakage reactance along with the increase of the magnetic shield thickness is revealed. On this basis
the influence of typical operating conditions of the SC
such as normal excitation
overexcitation and underexcitation
on the stator end leakage reactance is studied by combining the frozen permeability method (FPM) with the energy method. The variation law of the stator end leakage reactance along with the operating condition and magnetic shield thickness is revealed by analyzing the effect of the magnetic shield thickness on the end magnetic field and its energy under different operating conditions. The results show that the differences of the stator end loss and end leakage reactance are small when the magnetic shield thickness varies from 45 mm to 60 mm
thereby the magnetic shield thickness of 45 mm is optimal. The research results can provide a basis for selection of the magnetic shield thickness in the end region of the SC.