Experimental study of assembly foundation for transmission line tower in Taklimakan desert
|更新时间:2026-06-25
|
Experimental study of assembly foundation for transmission line tower in Taklimakan desert
Vol. 32, Issue 8, (2011)
作者机构:
1. 中国地质大学(北京)工程技术学院,北京,100083
2. 中国电力科学研究院 输变电工程力学研究所,北京,100192
作者简介:
基金信息:
DOI:
CLC:TU476+9
Online First:16 August 2011,
Published:2011
稿件说明:
移动端阅览
QIAN Zeng-zhen, LU Xian-long, DING Shi-jun. Experimental study of assembly foundation for transmission line tower in Taklimakan desert[J]. 2011, 32(8).
DOI:
QIAN Zeng-zhen, LU Xian-long, DING Shi-jun. Experimental study of assembly foundation for transmission line tower in Taklimakan desert[J]. 2011, 32(8).DOI:
Experimental study of assembly foundation for transmission line tower in Taklimakan desert
In order to obtain the performance of assembly foundations composed by the concrete footing slab and steel angle column
which are used for the transmission line engineering in Taklimakan desert
the four in-site full-scale of two sizes tests on the bearing capacity of assembly foundations combined uplift with horizontal loadings are carried out. The curves of load-displacement both of footing slab and foundation top plane
and the soil pressure on the footing slab are all obtained. For the foundation top plane
combined the uplift with horizontal loadings
the curve of uplift loading-displacement develops slowly; and the curve of horizontal loading-displacement increases linearly. The anti-overturning bearing capacity of assembly foundation is weak because of light dead weight of the steel support frame and the loose property of aeolian sand. The assembly foundation composed by concrete footing slab and steel angle column has a good property of coordinated performance. Influence of horizontal loading on bearing capacity of assembly foundation is obvious. According to the test data of ultimate uplift bearing capacity
the average frictional resistance of aeolian sand is 2.6 kPa
which is calculated by mechanical model of prismatic fracture plane.