Physicochemical properties of temperature indicating coating for temperature detection of encapsulated insulation layer of simulated dry-type transformer winding
|更新时间:2026-06-04
|
Physicochemical properties of temperature indicating coating for temperature detection of encapsulated insulation layer of simulated dry-type transformer winding
Vol. 45, Issue 6, (2026)
作者机构:
合肥工业大学电气与自动化工程学院,安徽,合肥,230009
作者简介:
基金信息:
DOI:
CLC:TM83
Published:2026
稿件说明:
移动端阅览
DONG Bingbing, CHEN Lingchan, MENG Yan. Physicochemical properties of temperature indicating coating for temperature detection of encapsulated insulation layer of simulated dry-type transformer winding[J]. 2026, 45(6).
DOI:
DONG Bingbing, CHEN Lingchan, MENG Yan. Physicochemical properties of temperature indicating coating for temperature detection of encapsulated insulation layer of simulated dry-type transformer winding[J]. 2026, 45(6).DOI:
Physicochemical properties of temperature indicating coating for temperature detection of encapsulated insulation layer of simulated dry-type transformer winding
Thermally induced defects in the encapsulated insulation layer of dry-type transformers are prominent. To detect abnormal heating of winding insulation materials in a timely manner
this paper proposes an inorganic thermochromic coating-based temperature measurement method for the encapsulated insulation layer of dry-type transformer windings and investigates its performance. The inorganic temperature-indicating material is synthesized via the liquid-phase method
and its structure and micromorphology are characterized by Fourier transform infrared spectroscopy
revealing the discoloration mechanism of the material. Considering the discoloration temperature range and sensitivity
the optimal mass ratio of the components (oxalic acid
potassium oxalate
and cobalt carbonate) is determined. Temperature-indicating coatings are prepared using two different basecoats
and their composition ratios are optimized according to discoloration
adhesion
hydrophobicity
and electrical properties. The results show that coatings using RTV-Ⅱ as the basecoat have a discoloration temperature of 103~120 ℃ and a grade 1 adhesion level. The static contact angle is greater than 100° both before and after discoloration
and the surface flashover voltage exceeds 9 kV/cm. The coating achieves the best comprehensive performance when the ratio of the basecoat to thermochromic material is 10∶3. After thermal aging at 60~80 ℃ for 168 h
no obvious degradation is observed in its discoloration and electrical insulation performance. The results can provide technical support for the temperature detection and overheating warning of thermally induced defects in the encapsulated insulation layer of dry-type transformer windings.