Current transfer characteristics of control switches in a DC controllable energy dissipation device
To limit the overvoltages of the flexible DC converter valves and absorb surplus energy
a DC controllable energy dissipation device based on metal oxide varistors has been applied for the first time in the Baihetan-Jiangsu ±800 kV hybrid cascaded ultra-high voltage direct current (UHVDC) transmission project. The control switches of the device consist of three types of switches connected in parallel
so the transient current transfer and distribution among the three control switches are critical to the safe operation of the device. Firstly
the operating conditions and current transfer characteristics of the control switches are analyzed. Theoretical calculations and electromagnetic transient simulations are performed on current transfer characteristics under a sinusoidal half-wave current waveform. The results show that after the fast switch is closed
the current in the thyristor switch branch can be rapidly transferred to the fast switch branch
and the thyristor turns off reliably. Furthermore
the current transfer characteristics among the control switches are validated via a synthetic test circuit
and the test results verify the accuracy of theoretical calculations and simulations. In the tests
the thyristor turn-off time is delayed by approximately 5.7 ms compared with the simulation results
mainly due to discrepancies in the nonlinear characteristics between the simulated and actual saturated reactors. This reduces the current transfer rate of the thyristor branch. After adjusting the saturated reactor parameters in the simulation
the thyristor turn-off time in the simulation lags the test result by about 1.8 ms. Finally
the current transfer characteristics between the control switches under engineering operating conditions are verified using the electromagnetic transient model of the Baihetan-Jiangsu hybrid cascaded UHVDC system. Under extreme operating conditions
the current through the fast switch branch accounts for approximately 30% of the total current.