Research on identification method and applicability analysis of power frequency impedance anomalies in front of smart electricity meter
|更新时间:2026-04-19
|
Research on identification method and applicability analysis of power frequency impedance anomalies in front of smart electricity meter
Vol. 63, Issue 4, (2026)
作者机构:
1. 国网福建省电力有限公司营销服务中心,福州,350013
2. 国网福建省电力有限公司,福州,350003
3. 国网信通亿力科技有限责任公司,福州,350003
作者简介:
基金信息:
DOI:
CLC:
Published:2026
稿件说明:
移动端阅览
LIN Hua, ZHAN Wen, GAO Chen, et al. Research on identification method and applicability analysis of power frequency impedance anomalies in front of smart electricity meter[J]. 2026, 63(4).
DOI:
LIN Hua, ZHAN Wen, GAO Chen, et al. Research on identification method and applicability analysis of power frequency impedance anomalies in front of smart electricity meter[J]. 2026, 63(4).DOI:
Research on identification method and applicability analysis of power frequency impedance anomalies in front of smart electricity meter
To accurately detect abnormal conditions of the power frequency impedance in front of smart electricity meters on low-voltage lines
it is necessary to conduct an in-depth analysis of the feasibility and adaptability of existing identification methods. Firstly
based on the single-phase loop impedance model of the low-voltage distribution network
this paper elaborates on the calculation principles and implementation steps of the loop impedance method
impedance parameter estimation method
and neighbor meter voltage impedance method. Then
a single phase multi-user electricity experiment platform is constructed to collect electricity meter voltage and current data under different states of the meter front line (switch). Finally
the feasibility and adaptability of the three identification methods are evaluated based on experimental data and actual electricity meter data from the distribution area. The study shows that the loop impedance method is only suitable for systems with relatively small loop impedance
requiring the load of the downstream meters to remain unchanged between two measurement instances
which is quite demanding on the data. The impedance parameter estimation method is not affected by system impedance
but its identification results depend on the size and variation of its own load
with a significant deviation between the estimated value and actual value. The neighbor meter voltage impedance method is simple and easy to implement
has a wide range of applications
requires less data
and has a low false positive rate
but is only applicable to scenarios with multiple meter positions.