Research on error analysis and calibration technology of current transformers under the influence of DC bias magnetization
|更新时间:2026-02-02
|
Research on error analysis and calibration technology of current transformers under the influence of DC bias magnetization
Vol. 63, Issue 1, (2026)
作者机构:
1. 深圳供电局有限公司,广东,深圳,518001
2. 南方电网科学研究院有限责任公司,广州,510663
3. 广东省电网智能量测与先进计量企业重点实验室,广州,510663
作者简介:
基金信息:
DOI:
CLC:
Published:2026
稿件说明:
移动端阅览
尹仕红, 范小飞, 宋宏天, et al. Research on error analysis and calibration technology of current transformers under the influence of DC bias magnetization[J]. 2026, 63(1).
DOI:
尹仕红, 范小飞, 宋宏天, et al. Research on error analysis and calibration technology of current transformers under the influence of DC bias magnetization[J]. 2026, 63(1).DOI:
Research on error analysis and calibration technology of current transformers under the influence of DC bias magnetization
the iron core of the current transformer is prone to saturation
causing the ratio error to shift towards negative direction and the phase error to shift towards positive direction
resulting in measurement inaccuracy. This paper discusses the principle of the impact of DC bias on the error of current transformers
introduces a new type of anti-DC bias current transformer
which has anti-DC bias function compared to traditional current transformers. The paper briefly describes the verification requirements
methods
and schemes of anti-DC bias current transformers
and conducts a large amount of experimental verification work. The paper also develops an AC / DC standard current transformer based on self-excited oscillation flux gate technology and magnetic integrator technology with an accuracy level of 0.02
which can measure both DC and AC
and has been applied in the error verification of anti-DC bias current transformers