桂小燕. Analysis and Countermeasure of Misoperation Caused by AC-DC Interference[J]. 2014, (3): 49-51.DOI:
Analysis and Countermeasure of Misoperation Caused by AC-DC Interference
摘要
通过对一起发变组保护误动事故的调查分析
发现其直流控制回路的电缆过长
分布电容过大
当交流串入直流系统时
会通过控制电缆的分布电容构成回路
产生电容电流
引起一些动作值较低的灵敏继电器发生误动作
并据此提出了防范措施。通过改进继电保护二次回路
提高非电量保护启动功率
缩短直流控制电缆的长度
避免了此类问题的重复出现。
Abstract
Through the investigation on the accident resulted from generator-transformer unit misoperation
find that the length of the cable in protection loop is too long and the distributing capacitance of the cable is too big. When the severe mutual interference between DC and AC circuits effects as DC grounding
the sudden discharge of distributed capacitance
as a disturbance source
activates the output relay. Countermeasures are suggested
shorten the length of DC control cables
increase the voltage of intermediate output relay and breaker trip coil